Industrielle styresystemer - Wiki
To set up a MQTT publisher in codesys the following libraries are necessary to use:
The functionblock MQTT_Publisher was then created , with the following code:
FUNCTION_BLOCK MQTTPublisher
VAR_INPUT
topic : STRING(255);
xtrigger : BOOL;
message : STRING;
END_VAR
VAR
mqttPub : wagoappcloud.FbPublishMQTT_2(econnection := econnectionid.Connection1);
dwSize : DWORD;
aData : ARRAY[0..100] OF BYTE;
xRetain : BOOL := FALSE;
xError : BOOL := FALSE;
xBusy : BOOL := FALSE;
eQualityOfService : eQualityOfService := 1;
END_VAR
######################
wagosysplainmem.MemCopy(pDest:=ADR(aData),pSource:=ADR(message),udiSize:=TO_WORD(len(message)));
mqttPub(sTopic:=topic,eQualityOfService:=eQualityOfService,xRetain:=xRetain,dwSize:=TO_WORD(len(message)),aData:=aData,xTrigger:=xtrigger,xBusy=>xBusy,xError=>xError);
Before the PLC can publish to over MQTT, the WagoAppCloud settings needs to be changed to fit the system this is done by writing the PLC's IP into the searchbar of a web browser, then cloud connectivity → connection 1. The settings are set to: