To get control over the buttons we need to connect IO moduls:
...
Modul | Description | ||
---|---|---|---|
75x 2DI | for buttons "TakeAccept" and "GiveRefuse" | 1.0 is Take Accept and 1.1 is GiveRefuse | |
_75x2DO | not in use | ||
_75x8DI | for button "Request" and encoder | 2.2 is Request | |
_75x8DI_1 | for encoder | XCC AE7G10 | |
_75x8DO | not in use | Buttons Codes
When there is a need for the MR_Room (MR) to assume control from the BR_Room (BR), the following protocol is observed:
Initiation of Control Request:
The MR signals its intent to take control by setting MR_Request to TRUE. This serves as a formal request for control from BR to MR. This communication is directional; only the room currently without control can initiate this request.
Response to Control Request:
If BR_Accept is set to TRUE, control is granted to MR. Conversely, if BR_Refuse is set to TRUE, BR retains control, denying MR's request.
Control takeover:
Upon gaining control, MR_Rom is activated to, and both MR_Accept and MR_Refuse are reset to ensure MR has exclusive control.
System Timer Logic:
A timer associated with MR_Refuse is used to address potential inactivity. If there is no response within 10 seconds after MR's initial request, MR_Request is automatically set to FALSE, preventing the system from lingering in a waiting state.
Before BR_Request is set to TRUE, the system verifies the status of BR_ROOM to ensure that the timing and conditions are appropriate for transferring control. This protocol helps in sending requests when most effective, maintaining optimal system performance.
References:
https://www.wago.com/no/io-systemer/2-kanals-digital-inngang/p/750-400